Description
Products Description
Technical Description
Weight | 49 kg |
---|---|
Motor size | 150 |
Size | 450 mm |
Rotor surface | Painted black |
Electronics housing material | Die-cast aluminum |
Impeller material | Sheet aluminum |
Support plate material | Sheet steel, galvanized |
Support bracket material | Steel, painted black |
Inlet nozzle material | Sheet steel, galvanized |
Number of blades | 5 |
Direction of rotation | Clockwise, viewed toward rotor |
Degree of protection | IP55 |
Insulation class | "F" |
Moisture (F) / Environmental (H) protection class | H1 |
Max. permitted ambient temp. for motor (transport/storage) | +80 °C |
Min. permitted ambient temp. for motor (transport/storage) | -40 °C |
Installation position | See legend on product drawing |
Condensation drainage holes | On rotor side |
Mode | S1 |
Motor bearing | Ball bearing |
Technical features | - Output 10 VDC, max. 10 mA - Output 20 VDC, max. 50 mA - Output for slave 0-10 V - Operation and alarm display - Input for sensor 0-10 V or 4-20 mA - External 24 V input (parameter setting) - External release input - Alarm relay - Integrated PID controller - Power limiter - Motor current limitation - PFC, passive - RS-485 MODBUS-RTU - Soft start - Control input 0-10 VDC / PWM - Control interface with SELV potential safely disconnected from the mains - Thermal overload protection for electronics/motor - Line undervoltage / phase failure detection |
EMC immunity to interference | According to EN 61000-6-2 (industrial environment) |
EMC interference emission | According to EN 61000-6-3 (household environment), except EN 61000-3-2 for professionally used equipment with a total rated power greater than 1 kW |
Touch current according to IEC 60990 (measuring circuit Fig. 4, TN system) | <= 3,5 mA |
Electrical hookup | Terminal box |
Motor protection | Reverse polarity and locked-rotor protection |
Protection class | I (with customer connection of protective earth) |
Conformity with standards | EN 61800-5-1 / CE |
Approval | UL 1004-7 + 60730-1 / EAC / CSA C22.2 No. 77 + CAN/CSA-E60730-1 |
Data according to ErP directive
Installation category | A |
---|---|
Efficiency category | static |
Closed-loop speed control | ja |
Specific ratio* | 1,02 |
*Specific ratio = 1 + psf / 100 000 |
Actual | Request 2015 | ||
---|---|---|---|
Overall efficiency ηe | 69,2 | 59 | |
Efficiency grade N | 72,2 | 62 | |
Power input Pe | KW | 5,22 | |
Airflow qV | m3/h | 7865 | |
Pressure increase total | Pa | 1606 | |
Speed n | min-1 | 2620 | |
Data established at point of optimum efficiency |
Nominal data
Phase | 3~ | |
---|---|---|
Type of voltage | AC | |
Nominal voltage | in V | 400 |
Nominal voltage range | in V | 380 .. 480 |
Frequency | in Hz | 50/60 |
Type of data definition | maximum load | |
Speed | in min-1 | 2600 |
Power input | in W | 5250 |
Current draw | in A | 8 |
Min. ambient temperature | in °C | -25 |
Max. ambient temperature | in °C | 50 |
- online service
- Whatsapp:+8615627119954
- support@baizhouboms.com
-
We chat