| Weight | 89.1 kg |
|---|---|
| Motor size | 200 |
| Size | 630 mm |
| Rotor surface | Painted black |
| Electronics housing material | Die-cast aluminum |
| Impeller material | Sheet aluminum |
| Support plate material | Sheet steel, galvanized |
| Spacer material | Aluminum |
| Inlet nozzle material | Sheet steel, galvanized |
| Number of blades | 5 |
| Direction of rotation | Clockwise, viewed toward rotor |
| Degree of protection | IP55 |
| Insulation class | "F" |
| Ambient temperature note | Occasional start-up at temperatures between -40°C and -25°C is permitted. For continuous operation at ambient temperatures below -25°C (such as refrigeration applications), use must be made of a fan design with special low-temperature bearings. |
| Moisture (F) / Environmental (H) protection class | H1 |
| Max. permitted ambient temp. for motor (transport/storage) | +80 °C |
| Min. permitted ambient temp. for motor (transport/storage) | -40 °C |
| Installation position | See legend on product drawing |
| Condensation drainage holes | On rotor side |
| Mode | S1 |
| Motor bearing | Ball bearing / (sealed) |
| Technical features | - Output 10 VDC, max. 10 mA - Output 20 VDC, max. 50 mA - Output for slave 0-10 V - Operation and alarm display - Input for sensor 0-10 V or 4-20 mA - External 24 V input (parameter setting) - External release input - Alarm relay - Integrated PID controller - Motor current limitation - RS-485 MODBUS-RTU - Soft start - EEPROM write cycles: 100,000 maximum - Control input 0-10 VDC / PWM - Control interface with SELV potential safely disconnected from the mains - Thermal overload protection for electronics/motor - Line undervoltage / phase failure detection |
| EMC immunity to interference | According to EN 61000-6-2 (industrial environment) |
| EMC interference emission | According to EN 61000-6-4 (industrial environment) |
| Touch current according to IEC 60990 (measuring circuit Fig. 4, TN system) | <= 3,5 mA |
| Electrical hookup | Terminal box |
| Motor protection | Reverse polarity and locked-rotor protection |
| Protection class | I (with customer connection of protective earth) |
| Conformity with standards | EN 61800-5-1 / UKCA / CE |
| Approval | EAC / CSA C22.2 No. 77 + CAN/CSA-E60730-1 / UL 1004-7 + 60730-1 |
Data according to ErP directive
| Installation category | A |
|---|---|
| Efficiency category | static |
| Closed-loop speed control | ja |
| Specific ratio* | 1,01 |
| *Specific ratio = 1 + psf / 100 000 | |
| Actual | Request 2015 | ||
|---|---|---|---|
| Overall efficiency ηe | 68,5 | 60,4 | |
| Efficiency grade N | 70,1 | 62 | |
| Power input Pe | KW | 7,09 | |
| Airflow qV | m3/h | 15565 | |
| Pressure increase total | Pa | 1089 | |
| Speed n | min-1 | 1750 | |
| Data established at point of optimum efficiency | |||
Nominal data
| Phase | 3~ | |
|---|---|---|
| Type of voltage | AC | |
| Nominal voltage | in V | 400 |
| Nominal voltage range | in V | 380 .. 480 |
| Frequency | in Hz | 50/60 |
| Type of data definition | bei max. Wirkungsgrad | |
| Speed | in min-1 | 1750 |
| Power input | in W | 7060 |
| Current draw | in A | 10,8 |
| Max. ambient temperature | in °C | 40 |